CROSS Safety Report
Corrosion causes collapse of steel floodlight mast at football club
This report is over 2 years old
Overview
This is an alert that was issued by a local authority responsible for enforcing the Safety of Sports Grounds Act after a floodlighting mast collapsed at a football club's ground.
Key Learning Outcomes
For asset owners and operators of floodlights:
-
Inspection and maintenance regimes for floodlighting masts should include a risk assessment for internal corrosion of steel tubes
-
A check for internal corrosion should be carried out by a suitably qualified person where internal corrosion has been assessed as a significant risk
-
Inspection and maintenance regimes should include a check for cracking around any openings in tubular steel masts
-
Assessment of the structural adequacy of the floodlighting masts should include an assessment of the adequacy of any strengthening around openings in tubular masts
Full Report
Find out more about the Full Report
The Full Report below has been submitted to CROSS and describes the reporter’s experience. The text has been edited for clarity and to ensure anonymity and confidentiality by removing any identifiable details. If you would like to know more about our secure reporting process or submit a report yourself, please visit the reporting to CROSS-UK page.
This is an alert that was issued by a local authority responsible for enforcing the Safety of Sports Grounds Act with the full co-operation of the football club concerned, after a floodlighting mast collapsed at their ground (Figure 1). The mast consisted of a single column fabricated from five lengths of steel tube which successively reduced in diameter. The mast had an opening with a detachable cover just above ground level. The mast was believed to be of a bespoke design and installed in 1969. The mast had been painted externally but had no protective coating internally.
Factors contributing to collapse
Investigations have highlighted the following factors which contributed to the collapse:
-
Moisture was able to enter the inside of the mast through corroded and unsealed brackets supporting the floodlight lamps
-
Moisture was able to enter the inside of the mast through gaps between the detachable cover and the tubular section
-
Drainage holes at the bottom of the mast had become blocked allowing water to gather in the bottom of the mast
-
In addition to losing water by evaporation, water is likely to have been able to escape when it reached the level of the opening. This led to the internal face of the column corroding below the level of the opening leading to a significant reduction in the thickness of the steel tube.
-
A horizontal crack had developed in a corner at the top of the opening and it is possible that a similar crack had developed at the bottom of the opening (Figure 2)
-
Strengthening plates around the opening appear not to have been long enough to transfer load back into the body of the mast
Advice to other clubs
An inspection of other columns after their removal also revealed extensive corrosion below the level of the door openings. Advice from the reporter to other clubs is as follows:
-
Your maintenance regime for floodlighting masts at your ground should include a risk assessment for internal corrosion of steel tubes
-
A check for internal corrosion should be carried out by a suitably qualified person where internal corrosion has been assessed as a significant risk
-
Your maintenance regime should include a check for cracking around any openings in tubular steel masts
-
Your assessment of the structural adequacy of the floodlighting masts at your ground should include an assessment of the adequacy of any strengthening around openings in tubular masts
Submit a report
Your report will make a difference. It will help to create positive change and improve safety.
Our secure and confidential safety reporting system gives professionals the opportunity to share their experiences to help others.
Feedback
As part of a review after a light pole collapse in 2019, I inspected and investigated several galvanized steel light poles on the same site. A number showed signs of significant corrosion internally at the base (red for steel corrosion and white for galvanized corrosion) even though they were assumed to be less than 15 years old. The expected life would be upwards of 20 years before significant maintenance. I believe, although galvanized both internally and externally, accelerated corrosion had occurred due to blocked internal drainage, the build up of water internally and a more aggressive industrial environment. Significantly damaged poles were identified and suitably repaired. The light poles were a standard product by a well-known manufacturer. I believe this is a common problem and highlights the need for regular inspections and maintenance.
I don't think this identifies one of the key issues, as it is about the approach to mast and tower structures within sports grounds, and how they are singed off, as I have seen a number of structures which are not properly maintained, or have even been modified by the grounds keeper. I think it requires a step back to identify the reason it has got to this point. I think there may well be a bigger problem here, and classic of the person signing off just does not understand the implications.
CROSS Response
Your feedback discusses the importance of proper maintenance and controlling modifications. The reporter did discuss the importance of maintenance in their report, which is copied below.
Advice from the reporter to other clubs is as follows:
-
Your maintenance regime for floodlighting masts at your ground should include a risk assessment for internal corrosion of steel tubes.
-
A check for internal corrosion should be carried out by a suitably qualified person where internal corrosion has been assessed as a significant risk.
-
Your maintenance regime should include a check for cracking around any openings in tubular steel masts.
-
Your assessment of the structural adequacy of the floodlighting masts at your ground should include an assessment of the adequacy of any strengthening around openings in tubular masts.
Expert Panel Comments
Expert Panels comment on the reports we receive. They use their experience to help you understand what can be learned from the reports. If you would like to know more, please visit the CROSS-UK Expert Panels page.
This is a good example of the type of report CROSS continues to benefit from. Points to note are:
Lighting columns are often made of thin steel so the percentage loss of material due to minor corrosion may be significant in its effect on strength
The full stress demand will only occur in very high winds, or if resonance occurs. Consequently, the effects of weakening may not be noticed until it is too late i.e. with the risk of a mast failing suddenly
Wherever they are located, falling masts may injure but masts located in crowded places (like stadia) may be deemed to present a higher risk of injury consequence
In this case, the crack and its location are suspicious. Lighting columns have been known to oscillate and thence fail by fatigue. The risk of fatigue is enhanced by higher stress ranges consequent on thinning sections; by corrosion (giving stress concentrations) and at corners (again for stress concentrations). This crack is in a corner. Hence the advice to look for cracks in corners is very sound, not least as in this location, crack propagation rate is likely to accelerate with increasing crack length.
There have also been experiences of failures of tubes just below ground level, so there should be means to inspect the internal face when designing for the future. Also, steel will not corrode without oxygen so maintenance should include effective sealing of holes provided for fixings and the original drain holes provided for in galvanising processes.
There have also been experiences of failures of tubes just below ground level, so there should be means to inspect the internal face when designing for the future